We offer transformer bushings, disc insulator, high tension insulators that provides high electric insulation. These are suitable for both indoor as well as outdoor purposes. The salient features of the product includes
dimensional accuracy, efficient performance in complex weather conditions
and robust construction.
Transformer bushings 1.1 kv
We manufacture quality transformer
bushings of 1.1 KV that are designed for application on liquid filled power
transformers. These bushings are used to connect the power transformer to
overhead lines in either indoor or outdoor applications. We make these
bushings as per specifications.
 |
|
SC-B-0111
|
|
STANDARD PARTICULARS |
|
 |
| Drawing No. |
|
|
SC-B-0111 |
| Transformer Rating |
|
kV/Amp |
1.1 kV/250 |
|
|
|
Amp. |
|
| Part |
|
|
I |
II |
| Dimensions |
A |
mm |
50 |
60 |
|
B (Min.) |
mm |
14 |
20 |
|
C |
mm |
70 |
30 |
|
D |
mm |
45 |
50 |
|
E |
mm |
27 |
26 |
|
F |
mm |
34 |
30 |
| Power Frequency |
Dry |
kV |
12 |
| Withstand Voltage |
Wet |
kV |
10 |
| Net Weight (approx.) |
|
kg |
0.2 |
0.1 |
Applicable specification as per IS : 3347 Part-I &
IS : 7421
|
 |
 |
|
SC-B-0112
|
|
|
|
 |
| Drawing No. |
|
|
SC-B-0112 |
| Transformer Rating |
|
kV/Amp |
1.1 kV/400 |
|
|
|
Amp. |
| Part |
|
|
I |
II |
| Dimensions |
A |
mm |
70 |
85 |
|
B (Min.) |
mm |
22 |
28 |
|
C |
mm |
80 |
30 |
|
D |
mm |
55 |
70 |
|
E |
mm |
43 |
41 |
|
F |
mm |
49 |
46 |
| Power Frequency |
Dry |
kV |
12 |
| Withstand Voltage |
Wet |
kV |
10 |
| Net Weight (approx.) |
|
kg |
0.36 |
0.2 |
Applicable specification as per IS :3347 Part-I &
IS : 7421
|
 |
 |
 |
 |
|
SC-B-0113
|
SC-B-0113
|
SC-B-0113
|
|
|
|
 |
| Drawing No. |
|
|
SC-B-0113 |
| Transformer Rating |
|
kV/Amp |
1.1 kV/1000 |
|
|
|
Amp. |
| Part |
|
|
I |
II |
| Dimensions |
A |
mm |
90 |
110 |
|
B (Min.) |
mm |
32 |
37 |
|
C |
mm |
85 |
35 |
|
D |
mm |
55 |
90 |
|
E |
mm |
53 |
46 |
|
F |
mm |
67 |
57 |
| Power Frequency |
Dry |
kV |
12 |
|
| Withstand Voltage |
Wet |
kV |
10 |
|
| Net Weight (approx.) |
|
kg |
0.85 |
0.4 |
Applicable specification as per IS : 3347 Part-I &
IS : 7421
|
 |
|
|
|
 |
| Drawing No. |
|
|
SC-B-0111 |
| Transformer Rating |
|
kV/Amp |
1.1 kV/2000 |
|
|
|
Amp. |
| Part |
|
|
I |
II |
| Dimensions |
A |
mm |
104 |
125 |
|
B (Min.) |
Mm |
44 |
51 |
|
C |
mm |
85 |
35 |
|
D |
mm |
55 |
104 |
|
E |
mm |
66 |
64 |
|
F |
mm |
82 |
71 |
| Power Frequency |
Dry |
kV |
12 |
|
| Withstand Voltage |
Wet |
kV |
10 |
|
| Net Weight (approx.) |
|
kg |
1.25 |
0.6 |
Applicable specification as per IS : 3347 Part-I &
IS : 7421
|
 |
|
|
|
 |
| Drawing No. |
|
|
SC-B-0111 |
| Transformer Rating |
|
kV/Amp |
1.1 kV/2000 |
|
|
|
Amp. |
| Part |
|
|
I |
II |
| Dimensions |
A |
mm |
125 |
150 |
|
B (Min.) |
mm |
50 |
61 |
|
C |
mm |
85 |
35 |
|
D |
mm |
55 |
125 |
|
E |
mm |
86 |
80 |
|
F |
mm |
100 |
90 |
| Power Frequency |
Dry |
kV |
12 |
|
| Withstand Voltage |
Wet |
kV |
10 |
|
| Net Weight (approx.) |
|
kg |
1.5 |
0.8 |
Applicable specification as per IS : 3347 Part-I &
IS : 7421
|
 |
Post Insulator 11 kv & 22 kv
We offer Post insulators that have a
metal bolt down base as opposed to threads. Many early multipart lines are
spotted with line post insulators as replacements. Post insulators are also
used in substations to insulate high voltage switching gear and
transformers. These can be custom-made according to client's requirements.
 |
|
SC-PT-1101
|
|
STANDARD PARTICULARS |
|
 |
| Drawing No. |
|
|
SC-PT 1101 |
| Highest System Voltage |
|
kV |
12 |
| Working Voltage |
|
kV |
11 |
| Creepage Distance Minimum |
|
mm |
320 |
| Cantilever Strength |
Upright |
kg |
600 |
|
Underhand |
kg |
350 |
| Torsional Strength |
|
mkg |
30 |
| Compressive Strength |
|
kg |
3600 |
| Tensile Strength |
|
kg |
2000 |
| Power Frequency Withstand Voltage |
Wet |
kV |
40 |
|
Dry |
kV |
50 |
| Power Frequency Flash over Voltage |
Wet |
kV |
55 |
|
Dry |
kV |
65 |
| Impulse Withstand Voltage |
|
kVp |
75 |
| Power Frequency Puncture Voltage |
|
kV |
1.3xActual Flash over Voltage |
| Net Weight (approx.) |
|
kg. |
4.5 |
Specification as per IS : 2544, & IS : 5350
|
 |
 |
|
SC-PT-2201
|
|
|
|
 |
| Drawing No. |
|
|
SC-PT 2201 |
| Highest System Voltage |
|
kV |
24 |
| Working Voltage |
|
kV |
22 |
| Creepage Distance Minimum |
|
mm |
430 |
| Cantilever Strength |
Upright |
kg |
920 |
|
Underhand |
kg |
700 |
| Torsional Strength |
|
mkg |
70 |
| Compressive Strength |
|
kg |
4600 |
| Tensile Strength |
|
kg |
3000 |
| Power Frequency Withstand Voltage |
Wet |
KV |
60 |
|
Dry |
kV |
70 |
| Power Frequency Flash over Voltage |
Wet |
kV |
75 |
|
Dry |
kV |
85 |
| Impulse Withstand Voltage |
|
kVp |
125 |
| Power Frequency Puncture Voltage |
|
kV |
1.3xActual Flash over Voltage |
| Net Weight (approx.) |
|
kg. |
6.1 |
Specification as per IS : 2544, & IS : 5350
|
 |
 |
|
SC-PT-2202
|
|
|
|
 |
| Drawing No. |
|
|
SC-PT 2202 |
| Highest System Voltage |
|
kV |
24 |
| Working Voltage |
|
kV |
22 |
| Creepage Distance Minimum |
|
mm |
565 |
| Cantilever Strength |
Upright |
kg |
1815 |
|
Underhand |
kg |
1360 |
| Torsional Strength |
|
mkg |
230 |
| Compressive Strength |
|
kg |
6820 |
| Tensile Strength |
|
kg |
3060 |
| Power Frequency Withstand Voltage |
Wet |
kV |
70 |
|
Dry |
kV |
80 |
| Power Frequency Flash over Voltage |
Wet |
kV |
85 |
|
Dry |
kV |
95 |
| Impulse Withstand Voltage |
|
kVp |
150 |
| Power Frequency Puncture Voltage |
|
kV |
1.3xActual Flash over Voltage |
| Net Weight (approx.) |
|
kg. |
18 |
Specification as per IS : 2544, & IS : 5350
|
 |
Disc Insulator ( B & S Insulator, T &
C Type)
Our range of Disc Insulators (B &
S Insulator, T & C Type) with electro mechanical strength are provided
with reasonable power frequency. These insulators can withstand voltage and
power frequency of puncture voltage that ensures stable functioning. The
glaze applied is compressive in nature, adds to mechanical strength and
provides smooth surface for self-cleaning under contamination. We also
design these insulators as per client's requirements.
 |
 |
|
SC-DB-1102
|
SC-DB-1105
|
 |
 |
|
SC-D-1106 B70
|
SC-D-1107 B90
|
|
STANDARD PARTICULARS |
|
 |
| Drawing No. |
|
|
SC-DB-1102 |
| Porcelain Diameter |
|
mm |
255 |
| Spacing |
|
mm |
145 |
| Total Creepage distance |
|
mm |
320 |
| Combined Electro Mechanical Strength |
|
KN |
45 |
| Power Frequency one minute |
Wet |
kV |
40 |
| Withstand Voltage |
Dry |
kV |
55 |
| Impulse Withstand Voltage |
Negative |
kVp |
100 |
|
Positive |
kVp |
90 |
| Power Frequency Flash over |
Wet |
kV |
55 |
| voltage |
Dry |
kV |
65 |
| Impulse Flash over voltage |
Negative |
kVp |
110 |
|
Positive |
kVp |
100 |
| Puncture Voltage |
|
kV |
105 |
| Radio Influence Test Voltage RMS to Ground |
|
kV |
10 |
| Voltage Data Max Rl V at 1 MHz |
|
µV |
50 |
| Tongue & Clevis Type |
|
|
16 mm C |
| Net Weight (approx) |
|
Kgs. |
4.5 |
Specification as per IS : 731, BS : EN 60383 IEC : 383
|
 |
|
|
|
 |
| Drawing No. |
|
|
SC-DB-1105 |
| Porcelain Diameter |
|
mm |
255 |
| Spacing |
|
mm |
145 |
| Total Creepage distance |
|
mm |
320 |
| Combined Electro Mechanical Strength |
|
KN |
45 |
| Power Frequency one minute |
Wet |
kV |
40 |
| Withstand Voltage |
Dry |
kV |
55 |
| Impulse Withstand Voltage |
Negative |
kVp |
100 |
|
Positive |
kVp |
90 |
| Power Frequency Flash over |
Wet |
kV |
55 |
| Voltage |
Dry |
kV |
65 |
| Impulse Flash over voltage |
Negative |
kVp |
110 |
|
Positive |
kVp |
100 |
| Puncture Voltage |
|
kV |
105 |
| Radio Influence Test Voltage RMS to Ground |
|
kV |
10 |
| Voltage Data Max Rl V at 1 MHz |
|
µV |
50 |
| Tongue & Clevis Type |
|
|
16 mm C |
| Net Weight (approx) |
|
Kgs. |
4.5 |
Specification as per IS: 731, BS:EN 60383, IEC: 383
|
 |
|
|
|
 |
| Drawing No. |
|
|
SC-D-1106 B70 |
| Porcelain Diameter |
|
mm |
255 |
| Spacing |
|
mm |
145 |
| Total Creepage distance |
|
mm |
320 |
| Combined Electro Mechanical Strength |
|
KN |
70 |
| Power Frequency one minute |
Wet |
kV |
40 |
| Withstand Voltage |
Dry |
kV |
55 |
| Impulse Withstand Voltage |
Negative |
kVp |
100 |
|
Positive |
kVp |
90 |
| Power Frequency Flash over |
Wet |
kV |
55 |
| voltage |
Dry |
kV |
65 |
| Impulse Flash over voltage |
Negative |
kVp |
110 |
|
Positive |
kVp |
100 |
| Puncture Voltage |
|
kV |
105 |
| Radio Influence Test Voltage RMS to Ground |
|
kV |
10 |
| Voltage Data Max Rl V at 1 MHz |
|
µV |
50 |
| Ball & Socket Size |
|
|
16 mm B |
| Net Weight (approx) |
|
Kgs. |
5.5 |
Specification as per IS: 731, BS:EN 60383, IEC: 383.
|
 |
|
|
|
 |
| Drawing No. |
|
|
SC-D-1107 B90 |
| Porcelain Diameter |
|
mm |
255 |
| Spacing |
|
mm |
145 |
| Total Creepage distance |
|
mm |
320 |
| Combined Electro Mechanical Strength |
|
KN |
90 |
| Power Frequency one minute |
Wet |
kV |
40 |
| Withstand Voltage |
Dry |
kV |
55 |
| Impulse Withstand Voltage |
Negative |
kVp |
100 |
|
Positive |
kVp |
90 |
| Power Frequency Flash over |
Wet |
kV |
55 |
| voltage |
Dry |
kV |
65 |
| Impulse Flash over voltage |
Negative |
kVp |
110 |
|
Positive |
kVp |
100 |
| Puncture Voltage |
|
kV |
105 |
| Radio Influence Test Voltage RMS to Ground |
|
kV |
10 |
| Voltage Data Max Rl V at 1 MHz |
|
µV |
50 |
| Ball & Socket Size |
|
|
16 mm B |
| Net Weight (approx) |
|
Kgs. |
6.0 |
Specification as per IS: 731, BS:EN 60383, IEC: 383.
|
 |
|
|
 |